KMDAD series dryers can be mounted |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
to the floor or wall. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
PLC MONITOR |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
The mini PLC monitor shows the drying and regenerating cycle. |
|
|
|
|
|
|
|
|
|
|
|
|
Pressure Dewpoint |
-40°F |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Normal Inlet Temperature |
100°F |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Normal Working Pressure |
100 psi |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Maximum Inlet Temperature |
122°F |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Maximum Working Pressure |
230 psi |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Maximum Ambient Temperature |
122°F |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Pressure (psi)
Factor pressure F1 |
50 |
60 |
70 |
80 |
90 |
100 |
110 |
120 |
130 |
140 |
150 |
175 |
200 |
225 |
250 |
0.56 |
0.65 |
0.74 |
0.83 |
0.91 |
1 |
1.06 |
1.08 |
1.12 |
1.16 |
1.2 |
1.29 |
1.37 |
1.45 |
1.52 |
Intel temp (°F) Factor Inlet F2 |
70 |
80 |
90 |
100 |
105 |
110 |
115 |
120 |
- |
- |
- |
- |
- |
- |
- |
1.12 |
1.09 |
1.06 |
1 |
0.93 |
0.86 |
0.8 |
0.75 |
- |
- |
- |
- |
- |
- |
- |
CORRECTION SAMPLE: In order to properly size your dryer to the required task, you must take into account the specific conditions under which the dryer will be operating. Capacity of KMDAD series dryers assumes the following “standard conditions”: |
a. 100 psi operating pressure |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
b. 100°F operating temperature |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
By way of example, let’s assume that your customer required a flow of 100 cfm at an operating pressure of 100 psi, with an inlet temperature of 110°F. Pressure correction factor for 100 psi is 1 |
Inlet temperature correction factor for 100°F is .86 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Required dryer capacity calculation is 100 cfm / 1 / .86 = 116 cfm, so that the correct dryer to select is model KMDAD-120. |
|
|
|
|
|
|
|
|